Home » Products » Single Phase Watt-Hour Meter / KWH Meter (Kilowatt Hour Meter) » PS-3 Single Phase Electromechanical Watt-Hour Meter
PS-3 Single Phase Electromechanical Watt-Hour Meter

PS-3 Single Phase Electromechanical Watt-Hour Meter

The single phase electromechanical watt-hour meter is designed to meet latest IEC60521. With accuracy of class 2, it measures active energy in single-phase two-wire alternating current power grids.

Features of Single Phase Watt-Hour Meter
It is a reliable long life meter. The designed service life is 20 yeas and the maximal overload capacity is 800%Ib. The construction of the meter complies with BS5685 and protection class IP53 of IEC30529.

Components of Single Phase Watt-Hour Meter
1.Meter case

The meter case complies to the insulating protective-class Ⅱ.

2. Terminal block
The terminal block is molded of heat-and flame-resistant bakelite. It is fixed in the extended meter base. The voltage test link can be located inside or outside of the meter case.

3. Driving element
The driving element consists of a voltage element and a current element, both of which are fixed on the aluminum alloy frame. It has a load curve compensation device and inductive load adjustment mechanism.

4. Rotor
The rotor shaft is turned of high strength aluminum alloy. Bras or plastic worm is also available. The worm and shaft can be detached.

5. Braking element
The magnet is made of AINiCo5 alloy and designed as U-shaped so that the effect of short-time over currents upon the magnet is negligible.

6. Frame
The frame is die-casted by high-qualiy SiAl alloy of stable property to avoid distortion. A low load adjustment mechanism which can be manually adjusted is mounted on the frame.

7. Upper bearing
The upper bearing consists of a guide pin and a brass sleeve, and is fixed on the meter frame with one screw.

8. Lower bearing
The meter uses holistic hard ferrite magnetic bearing unless there is special request from the customer.

9. Register
The register adopts heat-and abrasion-proof plastic gears and bearings. No lubrication of bearings is needed during the service life. The drum is made of polycarbonate, and is pyrographed and printed by UV resistant alumina to ensure non-depigmentation.

Typical connection diagram of Single Phase Watt-Hour Meter

Outline & Installation Size of Single Phase Watt-Hour Meter

Technical Data of Single Phase Watt-Hour Meter

1 Meter type PS-3
2 Applicable Standards IEC60521. BS5685
3 Accuracy Class 2 (according to IEC60521)
4 Average service life (MTTF) 20 years
5 Basic current (lb) A 5 10 15
6 Maximum current (lmax) A 20 30 40 60 80 100
7 Reference voltage Un 110V,120V,220V,230V,240V
8 Reference frequency fn 50Hz, 60Hz
9 Power losses in voltage circuit at 50Hz Un For over load capacity of 800%lb:1.3W/6VA others:1.0W/5VA
10 Power losses in current circuit at 50Hz Un Ib <0.5VA
11 Non-running with no-load 0.8~1.1Un
12 Starting current 0.5%lb
13 Mean temperature coefficent: Form0.1lb to lmax at unity PF Form 0.2lb to lmax at unity 0.5lagging <0.08%/℃ <0.12%/℃
14 Insulation level: Withstanding A.C. voltage for 50Hz, 1min Withstanding impulse voltage 1.2/50us >4kV >8kV
15 Rated load torque at unity PF, lb Over load capacity 800%lb:350uNm Over load capacity 400~600%lb:400uNm
16 Weight of rotor 23.5g
17 Weight of meter 1.6kg
18 Main case Bakelite base/PC cover/bakelite terminal cover
19 Register Cyclometer single, unidirectional, Jumping
20 Option Reverse running stopper
Feedback Form
Other Products
Company Brief: Established in 1995, Geyu Machine Electricity Co., Ltd. is one of the leading manufacturers of low voltage electric equipment in China, such as KWH Meters (Kilowatt Hour Meters), Power Capacitors, Circuit Breakers and AC Contactors for buildings and industries. Our KWH Meters (Kilowatt Hour Meters), Power Capacitors and other products all meet ISO9001 standards, and meet the requirements of Implementation Rules for Compulsory Certification. We strive to balance environmental and economic objectives, integrating them into our business plan.